TT-25kV 600A T Deadbreak Connector is used to terminate high voltage underground cable to transformers, switches, switchgear and other apparatus. It is fully shielded, submersible. Our Systems offers an exclusive optional capacitive test point similar to test points on 200 A elbow connectors. This allows use of Fault Indicators. T connectors include the T Cable Connector and the loadbreak bushing extender. They also provides a convenient location for a M.O.V.E. arrester or grounding elbow. They available conductor cross section is 25-500mm’for 25kV cable.
Reference No. |
Conductor cross section (mm) |
Stretch range over insulation (mm) |
Cable Type |
Size of stress cone |
TT 15/600-25 |
25 |
16.6 |
8.7/15 |
A |
TT 15/600-35 |
35 |
17.6 |
8.7/15 |
A |
TT 15/600-50 |
50 |
19 |
8.7/15 |
A |
TT 15/600-70 |
70 |
20.6 |
8.7/15 |
B |
TT 15/600-95 |
95 |
22.2 |
8.7/15 |
B |
TT 15/600-120 |
120 |
23.6 |
8.7/15 |
B |
TT 15/600-150 |
150 |
25.2 |
8.7/15 |
C |
TT 15/600-185 |
185 |
26.7 |
8.7/15 |
C |
TT 15/600-240 |
240 |
29 |
8.7/15 |
D |
TT 15/600-300 |
300 |
31.2 |
8.7/15 |
D |
TT 15/600-400 |
400 |
34.4 |
8.7/15 |
E |
TT 15/600-500 |
500 |
37.2 |
8.7/15 |
F |
Reference No. |
Conductor cross section (mm) |
Stretch range over insulation (mm) |
Cable Type |
Size of stress cone |
TT 25/600-35 |
35 |
18.6 |
12/20 |
B |
TT 25/600-50 |
50 |
19.6 |
12/20 |
B |
TT 25/600-70 |
70 |
21 |
12/20 |
B |
TT 25/600-95 |
95 |
22.6 |
12/20 |
C |
TT 25/600-120 |
120 |
24.2 |
12/20 |
C |
TT 25/600-150 |
150 |
25.6 |
12/20 |
C |
TT 25/600-185 |
185 |
27.2 |
12/20 |
D |
TT 25/600-240 |
240 |
28.7 |
12/20 |
D |
TT 25/600-300 |
300 |
31.1 |
12/20 |
E |
TT 25/600-400 |
400 |
33.2 |
12/20 |
E |
Reference No. |
Conductor cross section (mm) |
Stretch range over insulation (mm) |
Cable Type |
Size of stress cone |
TT 25/600-50 |
50 |
27.6 |
18/20 |
D |
TT 25/600-70 |
70 |
29.2 |
18/20 |
D |
TT 25/600-95 |
95 |
30.6 |
18/20 |
D |
TT 25/600-120 |
120 |
32.2 |
18/20 |
E |
TT 25/600-150 |
150 |
33.7 |
18/20 |
E |
TT 25/600-185 |
185 |
36.1 |
18/20 |
E |
TT 25/600-240 |
240 |
38.2 |
18/20 |
F |
TT 25/600-300 |
300 |
27.6 |
18/20 |
F |
NOTE: The cable range is the basic element for choosing the product's type. The conductor size is just for a reference.
GET A QUOTE