LZJC-10 Current Transformer for Small Switchgear is a current measurement device designed for 6~35kV air-insulated switchgear. It is widely used for current measurement, protection and monitoring in power systems. Especially for small switchgear, it is favored for its compact design and efficient performance.
Characteristic of structure
The iron core, the primary winding and the secondary windingare all enclosed in the epoxy resin casting body. The sign ofoutput terminal is Pi and P2. The output terminal of the secondarywindings(the first one, Measurement Class)is 1S1, 1S2, Theoutput terminal of the secondary windings (the second one,Protection Class)is 2S1, 2S2. The four holes below the casting arefor installing.
Technical data |
|
Rated insulation level |
12/42/75kV |
Power factor of load |
COSФ =0.8(lagging) |
Rated secondary current |
5A or 1A |
Rated frequency |
50 or 60Hz |
Anti-Pollution grade |
Class ll |
Ambient temperature |
-5 ℃-40℃,daily average temperature not more than 30℃ |
Altitude |
≤1000m |
Standard |
GB 1208-2006 |
Type |
Rated primary current |
Accuracy class combination |
rated output |
Accuracy Coefficient |
1s thermal current(KA) |
Rated dynamic current |
||
0.2Class |
0.5Class |
10PClass |
||||||
LZJC-10 |
5 |
0.2/10P or 0.5/10P |
10 |
15 |
15 |
10 |
90 |
200 |
10 |
||||||||
15 |
||||||||
20 |
||||||||
30 |
||||||||
40 |
||||||||
50 |
||||||||
75 |
||||||||
100 |
||||||||
150 |
||||||||
200 |
||||||||
300 |
24.5 |
44 |
||||||
400 |
||||||||
500 |
32 |
59 |
||||||
600 |
||||||||
800 |
45 |
112.5 |
||||||
1000 |
GET A QUOTE